Online industry UPS 10KVA,15KVA,20KVA

Online industry UPS 10KVA,15KVA,20KVA
Product Detailed
Online industry UPS Model:FR-UK3110, 3115, 3120 Phase:3 phase in and single phase out Output isolation transformer,RS232/RS48

Name : Online industry UPS

Model:FR-UK3115

Topology : online double conversion

Phase : three phase in and single phase out

Capacity :15KVA

Main Feature:

-Online double conversion

-Output isolation transformer 

-Wide input voltage range

-Full protection function

-High reliability and performance

-Intelligent RS232 communication port

-Management software (optional)

-External battery bank (optional)

-SNMP adapter or USB (optional)

 Specification

MODEL 

FR-UK10/

FR-UK10L

FR-UK20/FR-UK20L

FR-UK30/ FR-UK30L

FR-UK50/FR-UK50L

FR-UK60/

FR-UK60L

FR-UK1110S/ FR-UK1110

FR-UK1115S/ FR-UK1115

 
 

INPUT

Voltage (Vac)

220/230/240V MODEL:165-275

110/120V MODEL: 85~137

 

Frequency (Hz)

50/ 60±5% (50/60Hz settings)

 

Phase

Single phase three wires

 

OUTPUT

Capacity(VA/W)

1000/700

2000/1400

3000/2100

5000/3500

6000/4200

10000/7000

15000/10500

 

Voltage range(Vac)

220/230/240±2% or 110/120±2%

 

Frequency (Hz)

50 / 60 ±0.5%(battery mode)

 

Waveform

Pure Sine wave,THD<3% (Linear load )

 

Transfer Time

0

 

Overload

125% load for 60 seconds , 150% load for 1second

 

BATTERY 

Voltage (Vdc)

48

192

 

BATT Type

4×7Ah12V/ External

8×7Ah12V/ External

16×7Ah12V/ External

16×7Ah12V/ External

16×7Ah12V/ External

32×7Ah12V/ External

48×7Ah12V/ External

 

Charger Current(A)Max

1/

4.5

1/

4.5

1/

4.5

1/

4.5

1/

4.5

3/

4.5

 

OTHER

Communication Interface

RS232,dry contactor  

( USB and SNMP adapter are optional)

 

Display

LCD display input voltage, output voltage, load capacity, battery voltage, etc.

LED indicates running status

 

Alarm

Overload, abnormal AC input, low battery

 

Protection

Low battery, overload, over temperature, short circuit, output over voltage, output low voltage

 

Noise ( dB )

≤55

 

Working Temperature

0~40°C

 

Relative humidity

0~95%(no condensation)

 

Dimension (mm) (W*D*H)

Standard/ Long backup

230×620 × 470

230×635× 690/230×620× 470

400×800×1180/

300×740×700

400×800×1180

 

Weight

(kg)

Standard/ Long backup

48/

36

74/

49

82/

56

90/

45

91/

47

210/

85

288/

145

 